                  Figure 3. Typical damages caused by insufficient confinement and detailing
               In addition to soft storey, significant damages are observed in the buildings
            having  torsional  irregularity,  short  columns  and  heavy  overhangs,  together
            with  the  impacts  of  other  inadequacies.  Damage  caused  by  the  short
            columns are commonly encountered in our country, it occurs as a result of
            not considering the short column effect in the design (Figure 4a). Overhangs
            are usually constructed in the RC buildings in our country in order to comply
            with the zoning and to gain space on the upper floors. If these overhangs are
            taken into account in the design and detailed accordingly, they would not
            create such negative effects in terms of structural behaviour. However, in our
            country, heavy overhangs cause damage since they are not considered in the
            calculations accurately and lead to the distortion of frame continuity (Figure
            4b). In the buildings with torsional irregularities, the elements on the outer