Seismic Isolation in Earthquake -
                              Resistant Structural Design for Resilient Cities















               Figure 15. Vertical displacements of isolators under earthquake loading in X, Y and Z
                                           directions
               The  ratios  of  the  resultant  floor  accelerations  obtained  in  the  analyses
            under the RSN181 record and the relative storey drift in the X and Y directions
            are given in Figure 16. As can be seen, floor accelerations have not dropped
            below 0.2 g limit in any floors
               which is specified in the circular of the Ministry of Health of Republic of
            Türkiye However, it reached the 0.3 g limit specified in the updated circular in
            2018 on the top floor, this limit was not exceeded. The relative storey drift rates
            remained below 0.005, which is the limit set in TBDY (2018) for Uninterrupted
            Use (KK), except for excessing in a small amount in the Y direction on the
            lowest floor.


























              Figure 16. Floor acceleration profile (X and Y direction junction) and relative storey drift
                                             ratio






                                                                 Year 2 / Issue 4 / July 2023  129